The following parameters can be set in the 'ABULiner' parameter level of the LIS-SV.
|
Parameter |
Designation |
See |
|
5.10 |
Calling up the parameter level |
|
|
5.11 |
Activating the LIS-SV for the ABULiner |
|
|
5.11 |
Setting the gear ratio |
|
|
5.12 |
Activating double lifting speed |
|
|
5.14 |
Setting the run-on time of the auxiliary fan |
|
|
Danger during setting work! During setting work on the LIS-SV, monitoring of the wire rope hoist is switched off. This means the wire rope hoist cannot be monitored for excess load, among other things. This means the wire rope hoist cannot be monitored for excess load, among other things. This in turn means the load could fall and kill or injure people! Do not use the crane for normal work during setting work, and only lift loads very carefully for test purposes! |
All LIS-SV parameters which are important for the ABULiner are combined in a separate parameter level, which is shown as a submenu.
|
|
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Open the menu of the
LIS-SV. See the documentation “Load indicator system LIS-SV”.
|
| |
|
Enter button |
Arrow buttons |
Select parameter 5.10.
Press ENTER.
● The 'ABULiner' parameter level is activated.
● Parameter 5.11 is displayed.
|
| |
|
Enter button |
Arrow buttons |
Select parameter 5.99.
Press ENTER.
● The previous parameter level is reactivated.
● Parameter 5.10 is displayed.
The LIS-SV is automatically activated for the ABULiner if a value is entered for the parameter 5.11.
In the ABULiner mode (a value is set for parameter 5.11):
─ The LIS-SV can monitor the total load for a maximum of two wire rope hoists.
─ Input F3 (normally used for measuring the load of wire rope hoist 3) now serves in monitoring the current rotational frequency of the hoist motor.
─ A value can be entered for parameter 3.0 (maximum load capacity of wire rope hoist 3). If a value is entered for this, parameter 5.11 cannot be set.
─ This interlocking thus excludes an incorrect setting.
─ The load-controlled switching point at output TxD of the LIS-SV cannot be used.
─ Parameter 4.5 (setting for load-controlled switching point) is not available.
In the normal mode (no value is set for parameter 5.11):
─ Operation of the ABULiner Lifting/Lowering unit is not possible.
─ The LIS-SV can monitor the total load for up to three wire rope hoists.
─ Input F3 serves in measuring the load of a third wire rope hoist.
─ A value can be entered for parameter 5.11 (gear ratio). If a value is entered for this, parameter 3.0 cannot be set.
─ This interlocking thus excludes an incorrect setting.
─ The load-controlled switching point at output TxD of the LIS-SV can be used.
─ Parameter 4.5 (setting for load-controlled switching point) can be used.
The LIS-SV uses the signal of the encoder and the gear ratio of the hoisting gear to calculate the hook travel distance, the maximum distance in the limit switch range and the current rotational frequency of the hoist motor. The gear ratio must be set on the machine.
|
| |
|
Cable speed |
|
Read off the type
designation at the type plate of the wire rope hoist.
Read off the cable
speed.
From this table, select
the gear ratio that matches the cable speed.
|
|
Cable speed | ||||
|
Hoist motor GM |
32 m/min at 50 Hz |
25 m/min at 50 Hz |
20 m/min at 50 Hz |
16 m/min at 50 Hz | |
|
800.4 |
50.01 |
63.49 |
77.77 |
98.16 | |
|
800.5 |
47.03 |
60.04 |
74.66 |
95.03 | |
|
1000.6 |
54.43 |
68.91 |
84.00 |
105.1 | |
|
1000.7 |
54.60 |
68.06 |
81.45 |
104.6 | |
|
2000.3 |
58.22 |
74.23 |
91.19 |
118.4 | |
|
3000.4 |
73.61 |
93.92 |
118.4 |
152.9 | |
|
5000.3 |
85.14 |
109.3 |
132.8 |
169.0 | |
|
5000.4 |
80.20 |
104.9 |
127.7 |
160.6 | |
|
6000.3 |
94.69 |
118.5 |
149.6 |
182.7 | |
|
7000.1 |
118.0 |
148.3 |
182.6 |
232.0 | |
Table: Gear ratios (numerical values) depending on hoist motor (lines) and cable speeds (columns) at 50 and 60 Hz.
|
| |
|
Enter button |
Arrow buttons |
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Select parameter 5.11.
Press ENTER.
● The set value is displayed.
If the value is 0.00, the function is deactivated.
● Hold ENTER pressed.
● CODE is displayed.
Hold ENTER pressed.
|
| |
|
Enter button |
Arrow buttons |
Enter the code 1443.
Press ENTER briefly.
|
| |
|
Enter button |
Arrow buttons |
Set the value from the
table.
If the display ‘0.00’ cannot be changed, a value is set in parameter 3.0. In this case, set the value to zero first.
Press ENTER briefly.
Below is a comprehensive, SEO-optimized article written around this keyword, aimed at fans, testers, and curious players. In the sprawling underground world of indie visual novels and fan-made horror games, few titles generate as much whispered curiosity as "Babysitter -Final v0.2.2b- -T4bbo-" . With its cryptic version tag and the mysterious “T4bbo” signature, this game has slowly built a reputation as a tense, branching narrative experience. But what exactly is it? Why has version v0.2.2b invoked “final” in its title? And who—or what—is T4bbo? What Is "Babysitter -Final v0.2.2b- -T4bbo-"? At its core, "Babysitter" is a choice-driven interactive drama (often leaning into psychological horror or thriller elements, depending on the build). The player assumes the role of a teenager or young adult hired to watch over a child in an isolated house. However, as the night progresses, strange events, unsettling phone calls, and the child’s increasingly bizarre behavior reveal that nothing is as it seems.
The version identifier suggests the developer intended this to be the last public release of the 0.2.x branch. The “b” suffix typically denotes a minor hotfix or beta patch. The inclusion of “Final” is intriguing: it may indicate that version 0.2.2b concludes a story arc, or that the developer (possibly named “T4bbo”) is moving on to a new project. Babysitter -Final v0.2.2b- -T4bbo-
Strengths: Tense atmosphere, meaningful choices, memorable sound design, multiple endings. Weaknesses: Short playtime (~2-3 hours per route), occasional cryptic puzzle logic, requires patience for the slow pacing. But what exactly is it
Given the structure—including version numbering ( Final v0.2.2b ), a dash-enclosed suffix ( -T4bbo- ), and the platform-typical formatting—this keyword strongly suggests a , visual novel , or unofficial interactive title , likely distributed via communities like itch.io, Telegram, Discord, or fan forums. There is no widely recognized commercial game by this exact name; instead, this appears to be a niche, possibly adult-oriented or horror-tinged indie project, where T4bbo might refer to a developer alias or a character name. What Is "Babysitter -Final v0
Just don’t play it while you’re actually babysitting. Have you played Babysitter v0.2.2b? What are your theories about T4bbo? Share your ending experiences in the comments below.
is more than a version number—it’s a snapshot of an indie creator’s vision at a pivotal moment. Whether you’re a horror connoisseur, a fan of branching narratives, or simply intrigued by the tag “T4bbo,” this game deserves a quiet night, headphones on, and lights dimmed.
The auxiliary fan of the hoist motor continues to run for several minutes after the lifting or lowering. This ensures that the hoist motor is adequately cooled even at slow lifting speeds. The run-on time can be adjusted.
|
| |
|
Enter button |
Arrow buttons |
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Select parameter 5.14.
Press ENTER.
● The set value is displayed.
|
| |
|
Enter button |
|
Set the value to between 3
and 10 minutes using the arrow buttons.
Press ENTER.